Stenner PCM Time Adjustable Controller
Stenner PCM Time Adjustable Controller
How It Works:
The PCM is a time adjustable controller utilized with Stenner's fixed output pump and a pulsing dry contact water meter for applications requiring proportional injection. The water meter sends a signal to the PCM and the PCM actuates the pump to deliver the desired dose based upon water volume. The PCM is a component in Stenners Proportional Injection System.
Materials of Construction:
- Housings Polycarbonate
- Timer Microcontroller with triac output
- Turndown Ratio 10:1
- Input Signal Non-voltage dry contact water meter
- Reset Time Immediate
- Minimum Signal Durations 10 milliseconds
- Input Electrical 120V 60Hz
- No Load Current 0.45mA AC maximum
- Output Electrical
- Maximum device load, 1.8 amp at 120v
Customize Your Own Proportional Feed InstallationIndividually select a PCM, a Classic Series single head fixed output pump and water meter. NOTE: The PCM, meter and pump components are sold separately.
Features:
- Chemical resistant ABS plastic housing
- On-time duration set with knob adjustment with locking feature
- 10' power cord and jacketed signal input cable